- Asco 4000 Series Transfer Switch Manual
- Asco Transfer Switch Manual
- Asco 434 Transfer Switch Manual
- Asco Transfer Switch Manual Group 9
- Asco Transfer Switch 7000 Series
- 7000 Series Asco Transfer Switch Manual
Largest online selection of indoor and outdoor, automatic and manual, emergency transfer switches. We carry the full line of ASCO and GE Zenith automatic and manual transfer switches with the best pices in the USA. We will beat any real written quote as long as we make a profit on the sale. 30 Amp to 3000 Amp switches. Building on the almost legendary reliability of the ASCO Series 300 Automatic Transfer Switch, ASCO is proud to announce the Series 300G. The most advanced production AUTOMATIC transfer switch in the world. The ASCO series 300G has the programmability to meet the most advanced mission critical applications. ASCO 7000 Series Power Transfer Switch Features. Conventional two-position transfer configuration, plus closed and delayed transition modes of operation. All configurations available with either automatic or non-automatic control. Listed to UL 1008 Transfer Switch Equipment for Automatic Transfer Switches and Certified to CSA 22.2, No.
Size:Download
Series 300
We Keep Your Power On fi
Power Transfer Switches
Power Outage Protection
Where would you be without a constant flow of electrical power? We often take for granted that power will always be around when we need it. In reality, power failures are very common. And when the power goes out, your business suffers. Power failures are unpredictable. They can occur at any time and for any number of reasons— a bolt of lightning, a power surge, a blackout, an accident or even equipment failure. They come without warning and often at the most inconvenient times.
It s for this reason that many businesses and other entities have invested in emergency power backup systems. Typically, the system consists of an engine generator and an automatic transfer switch (ATS) which transfers the load from the utility to the generator.
An ATS with built-in control logic monitors your normal power supply and senses any interruptions. When the utility power fails, the ATS automatically starts the engine and transfers the load after the generator has reached proper voltage and frequency. This happens in a matter of seconds after the power failure occurs. When the utility power has been restored, the ATS will automatically switch the load back, and after a time delay, it will shut down the engine. With an Automatic Transfer Switch, you are protected 24 hours a day, seven days a week.
Series 300 Power Transfer Switches Typical Applications
Telecom
In the telecommunications industry, providing a high level of service and dependability is crucial. Lost power means an interruption in service for your customers and lost business for your company. For instance, with cell sites scattered across a wide geographical region and in many remote areas, the chances of an interruption in power are increased, making Automatic Transfer Switches a valuable resource at each location. To maintain dependable service, each cell site must be monitored 24 hours a day. This can be very difficult without some type of remote monitoring and testing capability. The Series 300 Transfer Switch, combined with ASCO s monitoring and control management system, is a cost-effective, packaged solution which can help meet both of these challenging objectives without a major investment at each cell site. With ASCO s connectivity solutions you can remotely monitor and control numerous sites from around the corner or around the world.
Commercial/Retail, Light Industrial
The retail industry is very competitive. An electrical power failure can have a dramatic impact on a retailer s bottom line. If power is interrupted during peak shopping times, the effect could be extremely damaging to present and future business. A power interruption will not only suspend shopping, it can also create safety problems, result in lost transaction data, lost account information and damage to data collection equipment. In addition, retailers who rely on controlled climates to protect valuable inventory could suffer even greater losses, especially if the power failure occurs at a time when no one is available to rectify the situation. To avoid any of these power
outage problems, simply install a backup generator with an ASCO Series 300 Transfer Switch and power outage concerns will be a thing of the past.
Municipal
The ASCO Series 300 Transfer Switch can be a critical component of a municipal government s emergency power backup system. Residents of townships, cities and counties rely on police, fire, ambulance/first aid and other critical public sector services. An interruption in power would affect the ability of emergency services to effectively respond to the needs of the community. When time is a critical factor, such as when responding to a fire alarm or an emergency call, an ASCO Series 300 Transfer Switch can be a lifesaver, switching power to the backup generator. While not all municipal services are a matter of life and death, they are always expected to be there.
Agriculture
Maintaining electrical power is vital to an agriculture operation. If the flow of power is interrupted, your operation could be at risk unless the backup generator is quickly activated. A prolonged power outage can affect numerous aspects of the operation, from housing and feeding livestock to processing and producing the end product. With an ASCO Series 300 Transfer Switch, power will automatically be transferred over to your backup generator, eliminating the need to manually switch from utility to generator. When power is restored, the ASCO Series 300 Transfer Switch will, after an adjustable time delay to allow for utility stabilization, automatically switch the load back to the utility service.
Series 300 Power Transfer Switches
Maximum Reliability & Excellent Value
With a Series 300 Transfer Switch, you get a product backed by ASCO Power Technologies, the industry leader responsible for virtually every major technological advance in the Transfer Switch industry.
The ASCO Series 300 was designed for one purpose–to automatically transfer critical loads in the event of a power outage. Each and every standard component was designed
by ASCO engineers for this purpose.
The rugged construction and proven performance of the ASCO Series 300 assure the user of many years of complete reliability. The Series 300 is even designed to handle the extraordinary demands placed on the switch when starting or restarting stalled motors and switching high inrush loads.
ASCO s Series 300 modular, compact design makes it easy to install, inspect and maintain. All parts are accessible from the front so switch contacts can be easily inspected.
Features
lThe Series 300 is listed to UL 1008 standard for Transfer Switch Equipment and CSA standard C22.2 for automatic transfer switches.
lMeets NFPA 110 for Emergency and Standby Power Systems and the National Electrical Code (NEC) Articles 700, 701 and 702.
l 30 through 3000 amps in a compact design.l Available to 600 VAC, single or three phase.
lTrue double-throw operation: The single solenoid design is inherently interlocked and prevents contacts from stopping between sources or from being in contact with both sources at the same time.
UL Listed Withstand & Close-On Ratings
Available Symmetrical Amperes RMS | |||
Switch Ratings | |||
When Used | When Used | ||
amps | Maximum | ||
With Specific | |||
With Current | |||
Voltage | Circuit Breakers | ||
Limiting Fuses | |||
@ 480V/60Hz | |||
30 - 200 | 200,000 | 480v/60Hz | 22,000 |
230 | 100,000 | 480v/60Hz | 22,000 |
260, 400 | 200,000 | 480v/60Hz | 42,000 |
600,800,1000,1200 | 200,000 | 600v/60Hz | 65,000 |
1600, 2000 | 200,000 | 600v/60Hz | 85,000 |
2600, 3000 | 200,000 | 600v/60Hz | 100,000 |
Notes: 1. Current – limiting fuse should be Class J type through 400 amps: use Class L type above 400 - amp fuse rating
2. Refer to publication 1128 for specific manufacture’s breakers
Fig. 1: ASCO Power Transfer Switch rated 200 amperes shown in Type 3R enclosure
lThere s no danger of the Series 300 ATS transferring loads to a dead source because the unique ASCO single-solenoid operator derives power to operate from the source to which the load is being transferred.
lEasy-to-read flush-mounted control and display panel provides LED indicators for switch position and source availability.
It also includes test and time-delay bypass switches as standard features.
lStandard engine exerciser for weekly automatic testing of engine generator set with or without load.
lAdjustable time-delay feature prevents switch from being activated due to momentary utility power outages and generator dips.
lSupplied with solid neutral termination. Optional switched neutral pole available.
l Accessory kits available.
l Available for immediate delivery.
Asco 4000 Series Transfer Switch Manual
lNow available for service entrance applications. Contact ASCO for assistance.
Designed to Fit Anywhere Java download for xp professional.
The ASCO Series 300 product line represents the most compact design of automatic power transfer switches in the industry. With space in electrical closets being at a premium, the use of wall or floor-mounted ASCO Power Transfer Switches assures designers optimum utilization of space.
All transfer switches through 2000 amps are designed to be completely front accessible. This permits the enclosures to be installed flush to the wall and still allows installation of all power cabling and connections from the front of the switch. Cable entrance plates are also standard on the 1600 and 2000 amp units to install optional side-mounted pull boxes for additional cable bending space.
Fig. 2: ASCO Power Transfer Switch
Asco Transfer Switch Manual
rated 200 amperes
Fig. 4: ASCO Power Transfer Switch
rated 1000 amperes
Fig. 5: ASCO Power Transfer Switch rated 2000 amperes shown in Type 3R enclosure
Fig. 3: ASCO Power Transfer Switch
rated 400 amperes
Fig. 6: ASCO Power Transfer Switch
rated 3000 amperes
5
Series 300 Microprocessor Controller
The ASCO Microprocessor Controller is used with all sizes of Power Transfer Switches. It represents the most reliable microprocessor controller in the industry and includes, as standard, all of the voltage, frequency, control, timing and connectivity functions required for most emergency and standby power applications.
Voltage & Frequency Sensing
lAdjustable three-phase, close-differential voltage sensing on normal source.
lNormal source pickup voltage is adjustable to 95% of nominal; drop-out is adjustable from 70% to 90% of nominal.
lFrequency sensing on emergency source. Pickup at 95% and dropout at 85% of nominal.
Time Delays
lAdjustable time delay to override momentary normal source outages to delay all transfer switch and enginestarting signals.
lTransfer to emergency time delay—Adjustable from 0 to 5 minutes for controlled timing of load transfer to emergency.
l Retransfer to normal timedelay—Adjustable to 30 minutes.
lFive-minute unloaded running time delay for emergency engine generator cool down.
lFour-second time delay to ignore momentary voltage and frequency transients during initial genset loading.
Fig. 8: Door-Mounted Control & Display Panel
Control and Display Panel
lEasy-to-read flush-mounted control and display panel provides LED indicators for switch position and source availability. It also includes test andtime-delay bypass switches.
Standard Selectable Features
lInphase monitor to transfer motor loads, without any intentional off time, to prevent inrush currents from exceeding normal starting levels.
l Engine exerciser to automatically test backup generator each week Includes control switch for testing with or without load.
lSelective load disconnect, double-throw contact to operate at an adjustable 0 to 20 second adjustable time delay prior to transfer and reset 0 to 20 seconds after transfer.
l 60 Hz or 50 Hz selectable switch.
l Three-phase/single-phase selectable switch.
Remote Control Features
Terminal provisions for connecting: l Remote test switch.
lRemote contact for test or for peak shaving applications. Circuit will be automatically bypassed if emergency source fails.
l Inhibit transfer to emergency.
l Remotetime-delay bypass switch.
Battery to | |
Maintain Engine | |
Exerciser Clock | |
Settings | |
Retransfer to | |
Simple and Accurate | Normal Adjustable |
Adjustment of | Time Delay |
Voltage, Frequency | |
and | |
Settings Without | |
Need for Meters | |
and Variable | Transfer to |
Power Supplies | |
Emergency Adjustable | |
Time Delay | |
Dip Switches for Enabling | |
Serial | |
Customer Control | Communication Port |
Interfaces | |
Fig. 9: Microprocessor Controller |
Performance Features
n 600 volt spacing per UL and CSA standards.
n Interfacing relays are industrial grade,plug-in type with dust covers.
n Meets or exceeds the requirements for Electromagnetic Compatibility (EMC).
lANSI C37.90A/IEEE472 Voltage Surge Test
lNEMA ICS-109.21 Impulse Withstand Test
lDigital circuitry isolated from line voltages
lIEC 801-2 Electrostatic discharge (ESD) immunity
lENV50140 and IEC 803-1: Radiated electromagnetic field immunity
lIEC 801-4 Electrical fast transient (EFT) immunity
l ENV50142 Surge transient immunity
lENV50141: Conducted radio-frequency field immunity
lEN55011: Group 1, Class A conducted and radiated emissions
l Optically isolatedRS-485 Serial Port
lEN61000- 4-11 voltage dips and interruptions immunity
Series 300 ATS Optional Accessories
Accessory 11BG
A programmable engine exerciser that provides for weekly or biweekly operation, includes one form C contact for source availability of normal and one contact for availability of emergency (contact rating 2 amps @ 30 Vdc, 0.5 amp @ 125 Vac resistive). The programmable engine exerciser incorporates a 7 day or 14 day time base with a digital readout display. Includes “with or without” load control switch for exerciser period.
Accessory 14AA/14BA
Auxiliary contacts to indicate position of main contacts.Two (2) for normal and two (2) for emergency position (one set is standard).
Accessory 44A
Strip Heater with thermostat for extremely cold areas to prevent condensation and freezing of this condensation. External 120 volt power source required.
Accessory 44G
Strip Heater with thermostat, wired to load terminals: 208-240, 360-380, 460-480, 550-600 volts. Contains wiring harnesses for all transfer switch sizes.
Accessory 72A
Communications Interface Module (RS-485) to allow local or remote communications with ASCO PowerQuest ® VPi orSiteWeb™ communication products.
ASCO Pulsarfi 450
The ASCO Pulsarfi 450 provides unparalleled protection from power surges and transients. It is ahigh-performance surge suppressor which limits large surges and transients through a unique array ofcomputer-matched metal oxide varistors (MOVs). Unique fourcavity sand packedUL94-5 volt rated housing, UL1449, UL1283, and CSA listed. Available as a separate product only for mounting by customer. Contact ASCO for ordering information.
Fig. 10: Programmable Engine Exerciser with Source Availability Contacts (Accessory 11BG)
Fig. 11: Strip Heater Kit
(Accessory 44G)
Field Conversion Kits for Series 300 Transfer Switches
Kit No. | Description | |
K629830 | Engine Exerciser and source availability contacts (Acc. 11BG) | |
Strip Heater Kit (125 watt) 120 volt (Acc. 44A) | ||
Strip Heater Kit (125 watt) | ||
K609027 | Cable Pull Box | |
Fig. 12: Pulsar 450 | ||
6 FT Extension Harness* | ||
* For | Surge Suppressor |
Ordering Information for Series 300 & 386 Transfer Switches
To order an ASCO Series 300 Power Transfer Switch, complete the following catalog number:
300 + B + 3 + 600 + N + 1 + X + C + 11CD + 480V 60 Hz
Product | Neutral | Poles | Amperes | Voltage | Controller | Options | Enclosure | Optional | Specific |
Code | Code | Blank Open Type | Accessories | Volt & Freq |
300 | Blank | 2 poles, | Continuous | A3 | 115 | Insert X | C | Type 1 | 11BG | This information |
Solid | 1 | rating | B3 | 120 | 1 | If optional | (Standard) | Programmable | is necessary | |
Neutral | C | 208 | accessories | Engine Exerciser | to allow correct | |||||
F | Type 3R | |||||||||
B1 | 3 poles, | 30, 70, 104, | D | 220 | are required | 14AA/14BA | control settings | |||
E | 230 | Enclosure | ||||||||
Switched | 3 | 150, 200, | F | 240 | Auxiliary Contacts | prior to shipment | ||||
230, 260, | H | 380 | G | Type 4 | (2 sets) | |||||
Neutral | ||||||||||
400, 6004, | J | 400 | Enclosure | 2 | 44A, 44G | |||||
K | 415 | |||||||||
8004, 10004, | L | 440 | Type 12 | Strip Heater | ||||||
12004, 1600, | M | 460 | L | w/Thermostat | ||||||
Enclosure2 | ||||||||||
2000 | N | 480 | 72A Comm | |||||||
Q | 575 | |||||||||
26004, 30004 | Type 3R | Interface Module | ||||||||
R | 600 | M | ||||||||
Secure | ||||||||||
Enclosure |
To order an ASCO Series 386 Transfer Switch, complete the following catalog number:
386 + | B | + | 3 | + | 600 | + | N | + | 1 | + | X | + | C | + | 9C/9D + 480V 60 Hz | ||||||
Product | Neutral | Phase | Amperes | Voltage | Controller | Options | Enclosure | Optional | Specific | ||||||||||||
Code | Poles | Code | Blank | Open Type | Accessories | Volt & Freq | |||||||||||||||
386 | A | 2 poles, | Continuous | A3 | 115 | Insert X | C | Type 1 | 6Q | This information | |||||||||||
Solid | 1 | rating | B3 | 120 | 1 | If optional | (Standard) | is necessary | |||||||||||||
Neutral | C | 208 | accessories | Control | to allow correct | ||||||||||||||||
30, 70, 100, | D | 220 | are required | F | Type 3R | 9C/9D | |||||||||||||||
3 poles, | control settings | ||||||||||||||||||||
B | 1 | E | 230 | Enclosure | |||||||||||||||||
3 | 150, 200, | Source | prior to shipment | ||||||||||||||||||
Switched | F | 240 | Type 4 | Availability Lights | |||||||||||||||||
Neutral | 230 260, | H | 380 | G | |||||||||||||||||
400, 6004, | J | 400 | Enclosure2 | 14AA/14BA | |||||||||||||||||
800 | 4 | , 1000 | 4 | , | K | 415 | Auxiliary Contacts | ||||||||||||||
L | 440 | L https://newrevolution959.weebly.com/blog/microsoft-office-2007-professional-torrent. Microsoft PowerPoint 2007 enables you to produce professional-looking presentations, with a comprehensive set of features that you can use to create and format your information. You can create and add designer-quality SmartArt graphics with only a few clicks of your mouse. Be more productive—upgrade from Office 2007 to Office 365 today. Get more done by upgrading to Office 365. With an Office 365 subscription, you can install all the newest Office applications on multiple PCs, Macs, and other devices. You also get 1 TB of OneDrive. | Type 12 | ||||||||||||||||||
1200 | 4 | , 1600, | M | 460 | 72A Comm | ||||||||||||||||
Enclosure2 | |||||||||||||||||||||
2000, 30004 | N | 480 | Interface Module | ||||||||||||||||||
Q | 575 | Type 3R | All Accessories | ||||||||||||||||||
R | 600 | M | |||||||||||||||||||
Secure | |||||||||||||||||||||
Enclosure |
Note: 1. Specify neutral code C for 260 and 400 amperes only.
2.Available 30-1000, and 1600 amps. Use Type 3R for 1200, 2000, 2600 and 3000 amp applications.
3.115-120 volt available30-400 amps only. For other voltages contact ASCO.
4.600-1200 amp only available in secure type 3R enclosure. Secure type provided as standard for2600-3000 amp.
Extended Warranties for Series 300 Transfer Switches
Catalog No. | Description |
2EXW300 | |
3EXW300 | |
4EXW300 | |
5EXW300 |
Dimensions & Shipping Weights for Series 300 & 386 Transfer Switches
UL Type 1 Enclosure (See notes below for information on Type 3R, 4 & 12 Enclosures)
Switch Rating | Phase | Neutral | Dimensions, In. (mm)3 | Approx. Shipping | ||||
amps | Poles | Code | Width | Height | Depth | Weight Lb. (kg)4 | ||
30, 70, 100*, 104 | 2 | A | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 69 | (32) | |
2 | B | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 73 | (33) | ||
150, 200 | ||||||||
3 | A | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 73 | (33) | ||
*series 386 only | ||||||||
3 | B | 17 1/2 (445) | 31 (787) | 11 5/8 (295) | 75 | (34) | ||
2 | A | 18 (457) | 48 (1219) | 13 (330) | 100 (45) | |||
230, 260, 400 | 2 | B7 | or C | 18 (457) | 48 (1219) | 13 (330) | 110 (50) | |
3 | A | 18 (457) | 48 (1219) | 13 (330) | 100 (50) | |||
3 | B7 | or C | 18 (457) | 48 (1219) | 13 (330) | 120 (55) | ||
2 | A | 34 (864) | 72 (1829) | 20 (508) | 450 | (204) | ||
600, 800, 1000 | 2 | B | 34 (864) | 72 (1829) | 20 (508) | 475 | (217) | |
3 | A | 34 (864) | 72 (1829) | 20 (508) | 475 | (217) | ||
3 | B | 34 (864) | 72 (1829) | 20 (508) | 500 | (228) | ||
2 | A | 38 (965) | 87 (2210) | 24 (610) | 685 | (312) | ||
1200 | 2 | B | 38 (965) | 87 (2210) | 24 (610) | 705 | (321) | |
3 | A | 38 (965) | 87 (2210) | 24 (610) | 705 | (321) | ||
3 | B | 38 (965) | 87 (2210) | 24 (610) | 725 | (328) | ||
1600, 20001,6 | 3 | A | 38 (965) | 87 (2210) | 24 (610) | 925 Photo collage creator app. Select a few photos and instantly get an awesome photo collage (a grid of photos). Incredibly easy to use, yet highly powerful and has many options to customize and make it personal. Main Features: Layouts Select from 100+ predefined layouts or create your own. Stickers Choose from over 100+ stickers. Search for more stickers on the internet right from the app. Text Over 55 different fonts. | (419) | |
3 | B | 38 (965) | 87 (2210) | 24 (610) | 975 | (441) | ||
2600, 30002 | 3 | A | 38 (965) | 91 (2311) | 60 (1524) | 1700 (771) | ||
3 | B | 38 (965) | 91 (2311) | 60 (1524) | 2135 (969) |
Series 300 & 386 External Power Connections
Asco 434 Transfer Switch Manual
Sizes UL-Listed SolderlessScrew-Type Terminals
Switch Rating | Ranges of |
(amps) | (Unless Specified Copper Only) |
30 - 230* | One #14 to 4/0 AWG |
260, 400 | Two 1/0 AWG to 250 MCM |
or One #4 AWG to 600 MCM | |
600 | Two 1/0 AWG to 600 MCM |
800, 1000, 1200 | Four 1/0 to 600 MCM |
1600, 2000 | Six 1/0 to 600 MCM |
2600 | Twelve 3/0 to 600 MCM |
3000 | Twelve 3/0 to 600 MCM |
Note: All Series 300 switches are furnished with a solid neutral plate (unless switched neutral configuration is specified) and terminal lugs. Specify A in catalog number to order a neutral plate on the series
386switches.
*200 and 230 amp rated switches for use with copper cable only.
Notes:
1.Unit is designed for top cable entry of emergency & load and bottom entry of normal. A cable pull box is also available for all top or bottom cable access when required (optional accessory kit #K609027). Not required for type 3R, 4 & 12 enclosures where available.
2.Enclosures for 2600, 3000 amps are free-standing with removable top, sides & back.
3.For type 3R, 4 & 12 dimensions, add the following values to the type 1 dimensions:
a)30, 70, 100, 104, 150, 200A–add 1.5 in (38 mm) to the height.
b)230, 260, 400A - add 1.5 in (38 mm) to the depth.
c)1200A–type 4 & 12 notavailable–use 1600 amp switch
d)1600A–add 3 in (76 mm) to the height and 10 in to (253 mm) to the width.
e)2000, 2600, 3000A–type 4 & 12 not available. (Consult ASCO) Type 3R add 4.68 in (118 mm) to the height add 2.0 in (51 mm) to the width and add 13 in (329 mm) to the depth.
4.For type 3R, 4 & 12 weights, add the following values to the type 1 weights:
Asco Transfer Switch Manual Group 9
a)30, 70, 100, 104, 150, 200A–add 15 lbs. (6.8 kg).
b)230, 260, 400, 600, 800, 1000A–add 40 lbs. (18.1 kg).
c)1600A–add 60 lbs. (27 kg).
d)2000A–3000A Type 4 & 12 not available. (Consult ASCO)
5.When temperatures below 32ºF can be experienced, special precautions should be taken, such as the inclusion of space heaters, to prevent condensation and freezing of this condensation. This is particularly important when environmental enclosures (Type 3R, 4 & 12) are ordered for installation outdoors.
6.Front connected design for 300 only, 386 dimensions are: 38'W - 91'H - 48'D.
Asco Transfer Switch 7000 Series
7.Neutral Code “B” for 230 ampares only.
7000 Series Asco Transfer Switch Manual
Next >= Page 1 =12